Modbus Commands
C-28
TIWAY I Gateway User Manual
C.4 Error Responses
Errors
such as illegal addressing or failure of communications with a PLC
are reported by exception responses. Exception responses replace the
expected response to a request and are recognized by the returned Function
Code with the top bit set high (see example in Figure C-37).
07 01 00000041 XXXX
Address Function Data Checksum
Request:
I000000
07 81 02 XXXX
Address Function Exception
Code
Checksum
Response:
Figur
e C-37
Exception
Response Frame
In this example, the request is for secondary node 07 to return the data for
65 (41 hex) coils starting at address 00, which is an illegal address for a
SIMA
TIC TI PLC. The response is an exception indicated by the Function
Code 81 (01 with the high bit set), with the exception code 02 indicating that
the data address was illegal.
NOTE:
The TIW
A
Y I network uses Exception Primitives. Exceptions sent by
SIMA
TIC TI PLCs are mapped to Modbus Exception Codes.
T
able C-6 list the exception responses that apply to the functions supported
by the TIW
A
Y I Gateway
.
T
able C-6
Exception Responses
Code Name Description
01 Illegal Function The function received is not defined for this
application [equivalent to SIMATIC TI
exception codes 00, 01, 06, 15].
02 Illegal Data Address The address contained in the data field is not
valid for the secondary being addressed
[equivalent to SIMATIC TI code 02]
03 Illegal Data Value The value passed in the data field is not
allowable for the secondary being addressed
[equivalent to SIMATIC TI codes 10, 19, 1D].