Building Technologies
Page 29 of 50 Last Revised: 4/11/2011
Parameter Parameter text Parameter Value Unit
Note: This parameter selects the HI/LO Overload mode for the power module. To change this you first need to set P10=1, and then back to 0
afterwards.
p205 Power unit application [0] Load duty cycle with high overload for vector drives
Note: Set P210 = 440V for demo units. This is not normally needed with installed drives.
p210 Drive unit line supply voltage 440 V
Note: To start motor commissioning, you must set P10 = 1
p10 Drive commissioning parameter filter [0] Ready
Note: Parameter 15 calls a macro function that defines the basic command strategy of the drive. I would not recommend changing this from 12, as it
can produce unwanted faults if set incorrectly.
p15 Macro drive unit 12.) Standard I/O with AS
p304[0] Rated motor voltage 400 Vrms
p305[0] Rated motor current 0.42 Arms
p307[0] Rated motor power 0.12 kW
p308[0] Rated motor power factor 0.79
p309[0] Rated motor efficiency 0 %
p310[0] Rated motor frequency 50 Hz
p311[0] Rated motor speed 1350 rpm
Note: Parameter 500 is a much simplified version of P1300, and if in doubt you can change this anytime.
p500 Technology application [0] Standard drive
p700[0] Command source selection [0] No Macro
Note: Digital Inputs Status
r722 CO/BO: CU digital inputs, status 0000_0000_0000_0000_0000_1000_0000_0000B
Note: Digital Outputs - setup & status
p730 BI: CU signal source for terminal DO 0 Control_Unit : r52.3
p731 BI: CU signal source for terminal DO 1 Control_Unit : r52.7
p732 BI: CU signal source for terminal DO 2 Control_Unit : r52.2
r747 CU, digital outputs status 0000_0000_0000_0000_0000_0000_0000_0000B
Note: Analog Inputs - setup & status
r755[0] CU analog inputs actual value in percent, AI0 (T. 3/4) 72.04 %
p756[0] CU analog inputs type, AI0 (T. 3/4) [4] Bipolar voltage input (-10 V ... +10 V)
Note: Analog Outputs - setup & status
p771[0] CU analog outputs signal source, AO0 (T 12/13) Control_Unit : r21
r774[0] CU analog outputs output voltage/current actual, AO0 (T 12/13) 0
p776[0] CU analog outputs type, AO0 (T 12/13) [0] Current output (0 mA ... +20 mA)
Note: The following three parameters are the default internal connections for DI-0 to DI-2 respectively. To reassign these inputs you first have to
'unplug' these parameters by setting to zero.
p840[0] BI: ON / OFF (OFF1) Control_Unit : r722.0
p1113[0] BI: Setpoint inversion Control_Unit : r722.1
p2103[0] BI: 1. Acknowledge faults Control_Unit : r722.2
p1000[0] Speed setpoint selection [2] Analog setpoint
Note: The Sinamics range of drives use RPM to define various values, and the Min speed is one of the most common. If in doubt, start with 300rpm
and then fine-tune later.
p1080[0] Minimum speed 300 rpm
p1082[0] Maximum speed 1500 rpm
Note: I would recommend setting the ramp-up & ramp-down values to 30 seconds initially, and fine tune as required.
p1120[0] Ramp-function generator ramp-up time 10 s
p1121[0] Ramp-function generator ramp-down time 10 s
p1200[0] FlyRest oper mode [0] Flying restart inactive
Note: Most customers prefer to set the drive to auto-restart after a fault or power failure. To accomplish this, set P1210 = 6. Note for high-level
interface, additional steps may need to be taken.
p1210 Automatic restart, mode [0] Inhibit automatic restart
Note: This parameter sets the load characteristic, but unlike P500, there are quite a few options and abbreviations. I would recommend option 2 for the
majority of fans and pumps.
p1300[0] Open-loop/closed-loop control operating mode [2] U/f control with parabolic characteristic
Note: To finish motor commissioning (and reset other parameters), set P3900 = 1. If you do not want to reset other parameters, set P3900 = 3.
p3900 Completion of quick commissioning [0] No quick parameterization