Parameter Parameter text Parameter Value Unit
p840[0] BI: ON / OFF (OFF1) Control_Unit : r1025.0
p1000[0] Speed setpoint selection [3] Fixed speed setpoint
Note: Fixed Frequency setpoints are cumulative, so ensure external relay logic energizes one input at a time. The ESM
overrides this rule and runs to the setpoint defined in P1015.
p1001[0] CO: Fixed speed setpoint 1 500 rpm
p1002[0] CO: Fixed speed setpoint 2 750 rpm
p1003[0] CO: Fixed speed setpoint 3 1000 rpm
p1004[0] CO: Fixed speed setpoint 4 1250 rpm
p1015[0] CO: Fixed speed setpoint 15 1500 rpm
p1020[0] BI: Fixed speed setpoint selection Bit 0 Control_Unit : r722.0
p1021[0] BI: Fixed speed setpoint selection Bit 1 Control_Unit : r722.1
p1022[0] BI: Fixed speed setpoint selection Bit 2 Control_Unit : r722.2
p1023[0] BI: Fixed speed setpoint selection Bit 3 Control_Unit : r722.3
p1113[0] BI: Setpoint inversion 0
p1210 Automatic restart, mode
[26] Acknowledging all faults and reclosing for an ON
command
p2103[0] BI: 1. Acknowledge faults 0
p3880 BI: ESM activation Control_Unit : r722.4
p3881 ESM setp source [1] Fixed speed setpoint 15 (p1015)
Note: The following read-only parameters are shown as handy points of interest. Do not try to program these into your drive.
r722 CO/BO: CU digital inputs, status 0000_0000_0000_0000_0000_1000_0000_0000B
r1024 CO: Fixed speed setpoint effective 0 rpm