Building Technologies
Page 43 of 50 Last Revised: 4/11/2011
Parameter Parameter text Parameter Value Unit
Note: To change P0595 you first need to set P0010 = 5, and then set P0010 back to 0 afterwards.
p595 Selecting technological units [5] Pa
p596 Reference quantity, technological units 500
p753[0] CU analog inputs smoothing time constant, AI0 (T. 3/4) 500 ms
p756[0] CU analog inputs type, AI0 (T. 3/4) [0] Unipolar voltage input (0 V ... +10 V)
p1015[0] CO: Fixed speed setpoint 15 1350 rpm
p1080[0] Minimum speed 300 rpm
p1113[0] BI: Setpoint inversion 0
p1210 Automatic restart, mode
[26] Acknowledging all faults and reclosing for
an ON command
Note: When using ECO mode, set P1335 = 100% to enable slip compensation for correct operation.
p1300[0] Open-loop/closed-loop control operating mode
[7] U/f control for a parabolic characteristic and
ECO
p1335[0] Slip compensation, scaling 100 %
p2200[0] BI: Technology controller enable Control_Unit : r722.0
Note: Set pressure setpoint to suit application. This example assumes a 0-500Pa range sensor is used (e.g. QBM66.202 hi-range).
p2201[0] CO: Technology controller, fixed value 1 200 Pa
p2253[0] CI: Technology controller setpoint 1 Control_Unit : p2201
p2264[0] CI: Technology controller actual value Control_Unit : r755[0]
p2267 Technology controller upper limit actual value 600 Pa
p2268 Technology controller lower limit actual value -50 Pa
p2280 Technology controller proportional gain 1.1
p2285 Technology controller integral time 35 s
p2292 CO: Technology controller minimum limiting 20 %
p2302 Technology controller output signal starting value 50 %
p3880 BI: ESM activation Control_Unit : r722.1
p3881 ESM setp source [1] Fixed speed setpoint 15 (p1015)
Note: The following read-only parameters are shown as handy points of interest. Do not try to program these into your drive.
r755[0] CU analog inputs actual value in percent, AI0 (T. 3/4) 71.34 %
r2260 CO: Technology controller setpoint after ramp-function generator 200 Pa
r2272 CO: Technology controller actual value scaled 356.72 Pa
r2294 CO: Technology controller output signal 0 %