Building Technologies
Page 33 of 50 Last Revised: 4/11/2011
Parameter Parameter text Parameter Value Unit
p1015[0] CO: Fixed speed setpoint 15 1350 rpm
p1113[0] BI: Setpoint inversion 0
p1210 Automatic restart, mode
[26] Acknowledging all faults and reclosing for an ON
command
p2103[0] BI: 1. Acknowledge faults 0
p3880 BI: ESM activation Control_Unit : r722.1
p3881 ESM setp source [1] Fixed speed setpoint 15 (p1015)
Note: The following read-only parameters are shown as handy points of interest. Do not try to program these into your drive.
r755[0]
CU analog inputs actual value in percent, AI0
(T. 3/4)
71.48 %
r722 CO/BO: CU digital inputs, status 0000_0000_0000_0000_0000_1000_0000_0000B