Important OSM/ESM Functions
2-22
Industrial Ethernet OSM/ESM Network Management
C79000-G8976-C137-08
Table 2-2
Status
Meaning Possible Cause Remedy
disabled (
1
) Observer function is
disabled.
starting (
1
) The Observer is
waiting for test frames
from the RM.
The Observer was
started but no RM
was found.
Check the cable and
device functions as
well as the correct
wiring between the
Observer and RM.
monitoring (
1
) The Observer
monitors the RM
function. This is the
normal state.
rm error : hardware fault(
2
)
rm cfg/hardware error
rm error : test frames missing
rm error : rm status mismatch
(
2
)
Error in the
functioning of the RM
Bad wiring , device
and/or wiring
defective
Check the wiring
between the
Observer and RM
according the
instructions. Check
whether cable and
device function
correctly. Problem
indicators are the
traffic and RM LEDs
and the statistics
counters of the ring
ports.
cfg error : more than one
observer
There is more than
one Observer in the
ring.
More than one
Observer in the ring.
Check the device
configuration. Only
one device may be
configured as the
Observer in the ring!
cfg error : more than one rm There is more than
one RM in the ring.
More than one RM in
the ring.
Check the device
configuration. Only
one device may be
configured as the RM
in the ring!
cfg error : rm sw-version The firmware on the
RM is incompatible.
Incompatible software
versions of Observer
and RM devices
Check the software
version of the RM.
cfg error : rm on wrong port The RM is connected
to the wrong port of
the Observer.
Wiring error Connect the
Observer to the RM
as described in the
instructions.
rm timeout The Observer is no
longer receiving test
frames.
Device and/or wiring
fault/error
Check whether cable
and device function
correctly. Problem
indicators are the
traffic LEDs and the
statistics counters of
the ring ports.
(
1
): do not appear in the event log table.
(
2
): in the protection mode, in addition to the event log entry, port 7
(port 3 on the OSM TP22 ESM TP40) is set to passive