IP 266 STEP 5 Programming
9.4.1 Cold S5-100U Restart
Before you can work with the IP 266 following a cold S5-100U restart, you must
wait for completion of the module's runup phase. You must program the waiting
time in OB 22, which executes after every "Power OFF/Power ON". The pro-
grammed waiting time must be at least 3 seconds.
Call wait loop
FB 27
END
Set timer
START
END
Timer 0
no
yes
Reset and enable
timer
START
Call the delay time FB.
JU FB 27
NAME DELAY
BE
Force RLO = 1 and load timer with 3 s
JC =M1
M1 L KT 300.0
SD T 0
Time-out after 3 s
SCHL AN T 0
JC =SCHL
Reset timer and enable with RLO = 0
AT0
RT0
AT0
L KT 001.0
SD T 0
BE
OB 22
FB 27 NAME:DELAY
EWA 4NEB 812 6057-02
9-11