Troubleshooting IP 266
Error Code
Recovery Procedures
Cross-
Reference
FB6 Error in position control loop
There is no change in the actual position even though the analog voltage
(setpoint speed) exceeds 5 V. The current operation is aborted and mode 4
(follow-up mode) automatically started. In follow-up mode, the position
controller is off. Follow-up mode can be terminated at any time. The
position controller is then reenabled.
Possible causes:
- Encoder not connected, incorrectly connected or defective
- The module's analog output is not wired
- The power section is not switched on or not enabled
- The axis is blocked by an obstacle of some kind or is jammed.
PLC failureFB7
Invalid path specificationFB8
Invalid tool offsetFB9
Invalid G function for dimensional unit "degrees"FBA
Path specification not in BCD codeFBB
EEPROM not programmable!FBC
EEPROM failure!FBD
Only one continuous loop permittedFD0
No end of loopFD1 Section 5.4.2
Section 5.1.7
Kap. 5.3.15
Section 5.4.2
Printing FEC
Printer not ready!FED
No data in EEPROM/RAM !FBE
10-16
EWA 4NEB 812 6057-02