Troubleshooting IP 266
Error Code
Recovery Procedures
Incorrect hardware limit switch polarity
The only permissible values are "0" (NO contact, positive) and "1"
(NC contact, negative). The IP 266 can detect an invalid parameter value
only when neither hardware limit switch is actuated at the instant at which
the machine data is entered. The hardware limit switches are also evalua-
ted when a rotary axis is used. If none have been connected, NO contacts
must be programmed.
F61
Maximum speed too high for this resolution
When a 5V encoder is used, the counter chip can count pulse trains with a
maximum baud rate of 500 kHz. At the specified maximum speed in con-
junction with the specified resolution [µm/pulse], this value is exceeded.
F62
Erroneous data transferF55
Erroneous data transferF56
Cross-
Reference
BREAK receivedF57
PCB (module) does not answerF58
Wrong baudrateF5A
Parity errorF5D
Overflow errorF5E
Frame errorF5F
Invalid range limit value
This error occurs only in conjunction with a rotary axis. The cause of error is
the same as that for error F07.
F66 Section 5.1.3
Invalid dimensional unit
Permissible dimensional units are millimeters, inches and degrees.
F68
10-10
EWA 4NEB 812 6057-02