Parameter
Description Unit
User
Setting
Min Default Max
Access
Level
P2240 Setpoint of PID-MOP % -200.00 10.00 200.00 2
r2250 CO: Output setpoint of PID-
MOP
% - - - 2
P2253 CI: PID setpoint - 0:0 0:0 4000:0 2
P2254 CI: PID trim - 0:0 0:0 4000:0 3
P2261 PID setpt. filter - 0.00 0.00 60.00 3
r2262 CO: Act. PID filtered setpoint % - - - 2
P2264 CI: PID feedback - 0:0 755:0 4000:0 2
P2265 PID feedback filter
timeconstant
s 0.00 0.00 60.00 2
P2267 Max. value for PID feedback % -200.00 100.00 200.00 3
P2268 Min. value for PID feedback % -200.00 0.00 200.00 3
P2269 Gain applied to PID feedback - 0.00 100.00 500.00 3
P2270 PID feedback function selector
- 0 0 3 3
P2271 PID transducer type - 0 0 1 2
r2272 CO: PID scaled feedback % - - - 2
r2273 CO: PID error % - - - 2
P2274 PID derive. time - 0 0 65535 2
P2279 PID neutral zone - 0.00 0.00 100.00 3
P2280 PID proportional gain - 0.000 3.000 65.000 2
P2285 PID integral time s 0.000 0.000 60.000 2
P2291 PID output upper limit % -200.00 100.00 200.00 2
P2292 PID output lower limit % -200.00 0.00 200.00 2
P2293 PID limit ramp time - 0.00 0.00 100.00 3
r2294 CO: Act. PID output % - - - 2
P2303 PID output offset - 0.00 0.0 4000.0 3
P2304 PID opening time - 0 60 65535 2
P2305 PID closing time - 0 60 65535 2
P2306 PID actuator direction - 0 1 1 2
P2370 Selection of motor staging
stop mode
- 0 0 1 2
P2371 Selection of external motor
configuration
- 0 0 8 2
P2372 Enable motor cycling - 0 0 1 2
P2373 Motor staging hysteresis % 0.0 20.0 200.0 2
P2374 Motor staging delay s 0 30 650 2
P2375 Motor destaging delay s 0 30 650 2
P2376 Delay override % 0.0 25.0 200.0 2
P2377 Delay override lockout timer s 0 30 650 2
P2378 Staging frequency f, %fMax % 0.0 50.0 120.0 2
r2379 CO/BO: Status of motor
staging
- - - - 2
P2380 Motor hours run s 0 0 100000 2
P2390 Hibernation frequency Hz 0 0 650.00 3
P2391 Hibernation timer s 0 0 650.00 3
P2392 Restart frequency Hz 0 0 650.00 3
Factory settings (P0010=30)
Parameter
Description Unit
User
Setting
Min Default Max
Access
Level
P0003 User access level - 0 1 4 1
P0010 Commissioning Parameter
filter
- 0 0 30 1
P0970 Factory reset - 0 0 1 1