Chapter 5 – Commissioning
Siemens Building Technologies, Inc. 31
Setting Parameters with the BOP or AOP
The following table describes the procedure for modifying parameter P1082, Maximum Motor
Frequency. Use this table as a guide for setting all other parameters with the BOP.
NOTE: You can change motor data parameters only if P0010=1. To start the motor, reset
P0010=0.
Modify P0004, parameter filter function:
Step Action Resulting display
1
Press
to access the parameters.
2
Repeatedly press
until Parameter Filter P0004 displays.
3
Press to access the parameter values level.
4
Press
or to display the required value.
5
Press
to confirm and save the value.
6 Only the motor parameters display for the user.
Modify an indexed value under P1082 – Setting the maximum motor frequency:
Step Action Resulting display
1
Press to access the parameters.
2
Repeatedly press
until Maximum Frequency P1082 displays.
3
Press
to access the parameter values level.
4
Press
to display the currently programmed value.
5
Press
or
to display the required value.
6
Press to confirm and save the value.