Chapter 6 – Programming
Siemens Building Technologies, Inc. 43
P0761, Width of deadband (V/mA) for analog inputs
P0761 defines the deadband for the analog inputs.
Setting range: 0 to 10V, or 0 to 20 mA
Factory setting: 0
NOTE: P0761[x] = 0: No enabled dead zone.
The dead zone runs from 0V (or 0 mA) to the value
of P0761, if the values of P0758 and P0760
(y-coordinate for analog input scaling) have the
same sign. The dead zone is enabled from the
intersecting point (x-axis with analog input scaling
curve) in both directions, if P0758 and P0760 have
different signs.
When using a configuration with neutral point in the
center, Fmin (P1080) should be zero. There is no
hysteresis at the end of the deadband.
Index:
P0761[0]: IN000=Analog input 1.
P0761[1]: IN001=Analog input 2.
ymax
y2
y1
x1
x2
%
V
mA
ymin
P761
10
20
-10
-20
Analog Outputs
SED2 converts status variables such as output
frequency, motor voltage, or present motor
current via D/A converters (DAC) within a
scaleable range. The analog outputs then
display their values.
NOTE: For accurate and consistent
performance of SED2 analog
outputs, if you are not connecting a
NI 1000 sensor then terminals 10
and 4 (NI 1000) must connect to
terminal 2 (0V).
AOUT1
D / A
V: 0 - 10 V
2 - 10 V
I: 0 - 20mA
4 - 20mA
13
12
AOUT2
D / A
V: 0 - 10 V
2 - 10 V
I: 0 - 20mA
4 - 20mA
27
26
Analog Output
r0770 - P0781
5192B03en
Figure 30. SED2 Analog Outputs 1 and 2.
Parameter Settings for AOUT1 and AOUT2 (Commissioning)
P0773
1 + 2
r0774
1 + 2
P0781
1 + 2
P0771
1 + 2
P0780
P0779
P0778
P0777
P0776
Function
SCAL
Output
Deadband
5
192Z27e
n
Output:
Current or
voltage
P0771, Physical status variable
Defines the physical status variable to display as an analog signal. Possible settings:
21 Present output frequency (scaled to P2000, Reference Frequency), (factory setting).
24 Present SED2 output frequency (scaled to P2000, Reference Frequency).