Communications Mode CP 523
The following procedure is recommended:
1. Enter the parameter setting data on the programmer in DB 1 and include sufficient comments.
2. Store DB 1 on diskette or hard disk.
3. Transfer DB 1 to the memory submodule.
Table 7-6. Setting the CP 523 Parameters in Interpretive Mode on the Memory Submodule
0 Parameter block 0
6 2400 baud
0 Even parity
0 No BUSY signal
1 RS-232-C (V.24) interface
0 7 data bits (11-bit frame)
0 Handshaking OFF
ExplanationEntry on the PG 685
: KS = 'Parameters for the serial';
: S = 'Interface';
: KS = ':0600100';
: S = 'Parameters XON/XOFF';
: KS = ':2';
: KH = 1113;
2 Parameter block 2
11
H
DC1 (XON character)
13
H
DC3 (XOFF character)
: S = 'Parameters for ASCII';
: KS = 'mode';
: S = ':720030000';
: KH = 0D0D;
7 Parameter block 7
2 Interpretive mode
0030
D
Character delay time 300 ms
000
D
Message frame length 0
0D0D
H
End-of-text characters
(two carriage returns)
7-20
EWA 4NEB 811 6044-02a
Kommentare zu diesen Handbüchern