Technical Description CP 523
2.4 Memory Submodule
In Print mode, you require a user submodule, which you must configure with the following data in
off-line mode using a programmer:
Message texts in DB 2 to 255
These DBs are independent of the DBs stored in the CPU. The DBs in the memory submodule
and the DBs in the CPU may have the same numbers.
Printer interface parameters and configuration data for the message texts in DB 1.
You can use two types of user submodule:
EPROM submodule
A UV erasing facility is required for erasing the submodule contents.
EEPROM submodule
Submodule contents can be overwritten using a programmer.
Table 2-3. Overview of Permissible User Submodules
Submodule Type Order No. Capacity
EPROM 8 Kbyte
EEPROM
6ES5 375 - 0LA21 16 Kbytes
6ES5 375 - 0LA15
6ES5 375 - 0LA41
6ES5 375 - 0LC31
32 Kbytes
8 Kbytes
6ES5 375 - 0LC41 16 Kbytes
6ES5 375 - 0LC11 2 Kbytes
2.4.1 Memory Submodule Evaluation
Several error flags can be stored by the CP in byte 0 in conjunction with the memory submodule.
Table 2-4. Error Flags in Conjunction with the Memory Submodule
Error Remedy
X1
H
Memory submodule defective 1. PLC POWER OFF
2. Plug in (new) memory submodule
3. PLC POWER ON
X2
H
No message texts configured Configure message texts
Wrong or defective user submodule
plugged in?
Contents of
byte 0
X= Value for other half-byte irrelevant