DeviceLogix
DeviceLogix is a Rockwell Automation technology that
allows a DeviceNet™ node to be programmed to execute a
sequence independently from the control for the main PLC/
IPC. A DeviceLogix enabled DeviceNet™ node can be used
in conjunction with a standard DeviceNet™ network, providing
simple distributed control functionality. Additionally it can
also be used in a standalone application, without a network
connection or PLC/IPC, to sequence pneumatic valves and
control I/O. Numatics has integrated this licensed technology
into its DeviceNet™ compatible valve island series, which
combine the functionality of a modular pneumatic valve
system with integrated I/O.
Programming of the DeviceLogix enabled node is done using
the industry standard DeviceNet™ commissioning software
tool RSNetWorx for DeviceNet from Rockwell Automation. The
programming software features an easily understandable graphics
environment where the users can simply “drag and drop” logic function
blocks (i.e. AND, NAND, OR, NOR, XOR, XNOR, RS LATCHES,
COUNTERS and TIMERS) onto a page and interconnect them to
develop the required sequence, or ladder logic programming can be used to develop a sequence. The programmed
sequence is downloaded to the node via standard DeviceNet communication connection, thus multiple nodes can
be programmed on the same network.
Technical Data
ELECTRICAL DATA VOLTAGE CURRENT
Node Power at Max. Brightness 24 VDC +/- 10% 70 mA
BUS Power 11-25 VDC 25 mA
Valves & Discrete I/O 24 VDC +/- 10% 8 A maximum
Power Connector Single key 4 pin 7/8” MINI type (male)
Communication Connector Single key 5 pin 7/8” MINI type (male)
LED's Module Status and Network Status
OPERATING DATA
Temperature Range (ambient) -23º to +50º C
Humidity 95% relative humidity, non-condensing
Vibration / Shock IEC 60068-2-27, IEC60068-2-6
Moisture Protection IP65, IP67 (with appropriate assembly and termination)
CONFIGURATION DATA
Communication Module Display used for setting Node Address, Baud Rate, Fault / Idle Actions, and all other system settings.
MCM (Manual Confi guration Module) Optional module containing DIP switches for setting node address and baud rate.
ARM
(Auto Recovery Module) Optional module that contains automatic recovery of system setting in the event of total or partial system failure includ-
ing embedded DeviceLogix logic instructions.
Maximum Valve-Solenoid Outputs 32
NETWORK DATA
Supported Baud Rates 125K Baud, 250K Baud, 500K Baud, with Auto-Baud detection
Supported Connection Type Polled, Cyclic, Change of State (COS) and combination Message Capability
Bus Connector Single key 5 pin 7/8” MINI type (male)
Diagnostics Power, short, open load conditions and module health are monitored and fail-safe device settings
Special Features Supports function block diagram and ladder logic programming
WEIGHT
DeviceLogix
Communication Module
252g
DESCRIPTION
REPLACEMENT
PART NUMBER
DeviceLogix
communications
module (node)
240-293