Appendix E: Device Data Format
Siemens Energy & Automation, Inc. 103
Dist.: Time T3 (Zone Z3) expired 95 ms since fault (-1 = no occurance)
Dist.: Time T4 (direct. zone) expired 96 ms since fault (-1 = no occurance)
Dist.: Time T5 (non-direct. zone)
expired
97 ms since fault (-1 = no occurance)
Dist.: Time T1B (Zone Z1B) expired 98 ms since fault (-1 = no occurance)
Dist.: Time T1L (Zone Z1L) expired 99 ms since fault (-1 = no occurance)
Distance Protection:
General Trip
100 ms since fault (-1 = no occurance)
Dist. Teleprotection:
Carrier reception
101 ms since fault (-1 = no occurance)
Dist. Teleprotection:
Carrier send
102 ms since fault (-1 = no occurance)
POTT teleprotection:
Transient block
103 ms since fault (-1 = no occurance)
Weak Infeed: General Trip 104 ms since fault (-1 = no occurance)
Switch-onto-fault: Fault
Detection L1
105 ms since fault (-1 = no occurance)
Switch-onto-fault: Fault
Detection L2
106 ms since fault (-1 = no occurance)
Switch-onto-fault: Fault
Detection L3
107 ms since fault (-1 = no occurance)
Switch-onto-fault: Trip 3pole 108 ms since fault (-1 = no occurance)
Overvoltage Trip: Stage U> 109 ms since fault (-1 = no occurance)
Overvoltage Trip: Stage U>> 110 ms since fault (-1 = no occurance)
Ext. trip via binary input: Trip 111 ms since fault (-1 = no occurance)
Ext. trip via binary input:
1pole L1
112 ms since fault (-1 = no occurance)
Ext. trip via binary input:
1pole L2
113 ms since fault (-1 = no occurance)
Ext. trip via binary input:
1pole L3
114 ms since fault (-1 = no occurance)
Ext. trip via binary input: 3pole 115 ms since fault (-1 = no occurance)
Ext. trip via binary input:
Without AR
116 ms since fault (-1 = no occurance)
Reserved 117–120 For future expansion
1. This register location represents the sequential registers and their numbers within the device itself; as illustrated in Figure 5.1 in Chapter 5, the data
register numbers in the Modbus Master and the DTU3005 unit itself will vary from these register numbers.
2. Status information for each parameter is transmitted in two bits. The status bit indicates status (true=1, false=0) for the parameter and the valid bit indi-
cates that the device has sucessfully updated the value in the status bit (true=1, false=0).
Device Command Data Retrieved From PLC (7SA513)
First Command Word (Command Word) Additional Command Words (Data or Value)
0 = No command Unused
1 = Time Sync 2nd Word: Time [ms] - (0-59999)
3rd Word: Time [h/m] - high byte: HH (1-24), low byte: MM (0-59)
4th Word: Date [m/d] - high byte: MM (1-12), low byte: DD (1-31)
5th Word: Date [y] - YY (00-99)
2 = Reset LEDs Unused
3 = Activate Parameter Set A Unused
4 = Activate Parameter Set B Unused
Real-Time Device Data Stored in PLC (7SA513) (Continued)
Function Register Location in
PLC Block
1
Range or Contents