Appendix E: Device Data Format
Siemens Energy & Automation, Inc. 109
Fault Date/Time (y) 12 Year: YY (00…99)
Interrupted current:
Phase L1 (I/I
n
)
13 ms since fault (-1 = no occurance)
Interrupted current:
Phase L1 (I/I
n
)
14 Low word
Interrupted current:
Phase L1 (I/I
n
)
15 High word
Interrupted current:
Phase L2 (I/I
n
)
16 ms since fault (-1 = no occurance)
Interrupted current:
Phase L2 (I/I
n
)
17 Low word
Interrupted current:
Phase L2 (I/I
n
)
18 High word
Interrupted current:
Phase L3 (I/I
n
)
19 ms since fault (-1 = no occurance)
Interrupted current:
Phase L3 (I/I
n
)
20 Low word
Interrupted current:
Phase L3 (I/I
n
)
21 High word
Fault in the power system 22 ms since fault (-1 = no fault)
General Trip of Device 23 ms since fault (-1 = no occurance)
General 1pole trip of device: Phase
L1
24 ms since fault (-1 = no occurance)
General 1pole trip of device: Phase
L2
25 ms since fault (-1 = no occurance)
General 1pole trip of device: Phase
L3
26 ms since fault (-1 = no occurance)
General 3pole trip of device 27 ms since fault (-1 = no occurance)
Emerg. O/C fault detection
L1 only
28 ms since fault (-1 = no occurance)
Emerg. O/C fault detection L1E 29 ms since fault (-1 = no occurance)
Emerg. O/C fault detection
L2 only
30 ms since fault (-1 = no occurance)
Emerg. O/C fault detection L2E 31 ms since fault (-1 = no occurance)
Emerg. O/C fault detection L12 32 ms since fault (-1 = no occurance)
Emerg. O/C fault detection L12E 33 ms since fault (-1 = no occurance)
Emerg. O/C fault detection
L3 only
34 ms since fault (-1 = no occurance)
Emerg. O/C fault detection L3E 35 ms since fault (-1 = no occurance)
Emerg. O/C fault detection L13 36 ms since fault (-1 = no occurance)
Emerg. O/C fault detection L13E 37 ms since fault (-1 = no occurance)
Emerg. O/C fault detection L23 38 ms since fault (-1 = no occurance)
Emerg. O/C fault detection L23E 39 ms since fault (-1 = no occurance)
Emerg. O/C fault detection L123 40 ms since fault (-1 = no occurance)
Emerg. O/C fault detection L123E 41 ms since fault (-1 = no occurance)
Emerg. O/C protection:
General Trip
42 ms since fault (-1 = no occurance)
Emerg. O/C protection:
Trip 1pole L1
43 ms since fault (-1 = no occurance)
Real-Time Device Data Stored in PLC (7SD512) (Continued)
Function Register Location in
PLC Block
1
Range or Contents