Appendix E: Device Data Format
126 Siemens Energy & Automation, Inc.
O/C protection I>> phase Trip 44 ms since fault (-1 = no occurance)
O/C protection I> phase Trip 45 ms since fault (-1 = no occurance)
O/C protection Ip phase Trip 46 ms since fault (-1 = no occurance)
O/C protection IE>> earth Trip 47 ms since fault (-1 = no occurance)
O/C protection IE> earth Trip 48 ms since fault (-1 = no occurance)
O/C protection IEp earth Trip 49 ms since fault (-1 = no occurance)
AR: Close command from
auto-reclose
50 ms since fault (-1 = no occurance)
AR: Definitive trip 51 ms since fault (-1 = no occurance)
Neg. seq. I. (I2) prot.: Trip 52 ms since fault (-1 = no occurance)
O/C protection I>>> phase trip 53 ms since fault (-1 = no occurance)
Supervision of starting time trip 54 ms since fault (-1 = no occurance)
CT Primary 55 0-50000
CT Secondary 56 1 or 5
Reserved 57-60 For Future Expansion
1. This register location represents the sequential registers and their numbers within the device itself; as illustrated in Figure 5.1 in Chapter 5, the data
register numbers in the Modbus Master and the DTU3005 unit itself will vary from these register numbers.
2. Status information for each parameter is transmitted in two bits. The status bit indicates status (true = 1, false = 0) for the parameter and the valid bit indi-
cates that the device has sucessfully updated the value in the status bit (true = 1, false = 0).
Device Command Data Retrieved From PLC (7SJ600)
First Command Word (Command Word) Additional Command Words (Data or Value)
0 = No command Unused
1 = Time Sync 2nd Word: Time [ms] - (0-59999)
3rd Word: Time [h/m] - high byte: HH (1-24), low byte: MM (0-59)
4th Word: Date [m/d] - high byte: MM (1-12), low byte: DD (1-31)
5th Word: Date [y] - YY (00-99)
2 = Reset LEDs Unused
Real-Time Device Data Stored in PLC (7SJ600) (Continued)
Function Register Location in
PLC Block
1
Range or Contents