Appendix E: Device Data Format
Siemens Energy & Automation, Inc. 97
Dist.: Fault detection phase L1,3,E 83 ms since fault (-1 = no occurance)
Dist.: Fault detection only phase
L2,3
84 ms since fault (-1 = no occurance)
Dist.: Fault detection phase L2,3,E 85 ms since fault (-1 = no occurance)
Dist.: Fault detection only phase
L1,2,3
86 ms since fault (-1 = no occurance)
Dist.: Fault detection phase L1,2,3,E 87 ms since fault (-1 = no occurance)
Dist.: Fault det. In forward direction 88 ms since fault (-1 = no occurance)
Dist.: Fault det. In reverse
direction
89 ms since fault (-1 = no occurance)
Dist.: Time T1 (Zone Z1) expired 90 ms since fault (-1 = no occurance)
Dist.: Time T2 (Zone Z2) expired 91 ms since fault (-1 = no occurance)
Dist.: Time T3 (Zone Z3) expired 92 ms since fault (-1 = no occurance)
Dist.: Time T4 (direct. zone) expired 93 ms since fault (-1 = no occurance)
Dist.: Time T5 (non-direct. zone)
expired
94 ms since fault (-1 = no occurance)
Dist.: Time T1B (Zone Z1B) expired 95 ms since fault (-1 = no occurance)
Dist.: Time T1L (Zone Z1L) expired 96 ms since fault (-1 = no occurance)
Distance Protection: General Trip 97 ms since fault (-1 = no occurance)
Dist. Teleprotection: Carrier recep-
tion
98 ms since fault (-1 = no occurance)
Dist. Teleprotection: Carrier send 99 ms since fault (-1 = no occurance)
POTT Teleprotection: Transient
block
100 ms since fault (-1 = no occurance)
Ext. trip via binary input: Trip 101 ms since fault (-1 = no occurance)
Ext. trip via binary input:
1pole L1
102 ms since fault (-1 = no occurance)
Ext. trip via binary input:
1pole L2
103 ms since fault (-1 = no occurance)
Ext. trip via binary input:
1pole L3
104 ms since fault (-1 = no occurance)
Ext. trip via binary input: 3pole 105 ms since fault (-1 = no occurance)
Ext. trip via binary input:
Without AR
106 ms since fault (-1 = no occurance)
Reserved 107–110 For future expansion
1. This register location represents the sequential registers and their numbers within the device itself; as illustrated in Figure 5.1 in Chapter 5, the data
register numbers in the Modbus Master and the DTU3005 unit itself will vary from these register numbers.
2. Status information for each parameter is transmitted in two bits. The status bit indicates status (true = 1, false = 0) for the parameter and the valid bit indi-
cates that the device has sucessfully updated the value in the status bit (true = 1, false = 0).
Device Command Data Retrieved From PLC (7SA511)
First Command Word (Command Word) Additional Command Words (Data or Value)
0 = No command Unused
1 = Time Sync 2nd Word: Time [ms] - (0-59999)
3rd Word: Time [h/m] - high byte: HH (1-24), low byte: MM (0-59)
4th Word: Date [m/d] - high byte: MM (1-12), low byte: DD (1-31)
5th Word: Date [y] - YY (00-99)
Real-Time Device Data Stored in PLC (7SA511) (Continued)