Appendix E: Device Data Format
Siemens Energy & Automation, Inc. 113
O/C Fault Detection L1-L3 44 ms since fault (-1 = no occurance)
O/C Fault Detection L1-L3-E 45 ms since fault (-1 = no occurance)
O/C Fault Detection L2-L3 46 ms since fault (-1 = no occurance)
O/C Fault Detection L2-L3-E 47 ms since fault (-1 = no occurance)
O/C Fault Detection L1-L2-L3 48 ms since fault (-1 = no occurance)
O/C Fault Detection
L1-L2-L3-E
49 ms since fault (-1 = no occurance)
O/C Fault Detection E only 50 ms since fault (-1 = no occurance)
O/C General Trip Command 51 ms since fault (-1 = no occurance)
50HS-Phase high-set element TRIP 52 ms since fault (-1 = no occurance)
50-Phase inst. element TRIP 53 ms since fault (-1 = no occurance)
51-Phase time element TRIP 54 ms since fault (-1 = no occurance)
50NHS-Ground high-set
element TRIP
55 ms since fault (-1 = no occurance)
50N-Ground inst. element TRIP 56 ms since fault (-1 = no occurance)
51N-Ground time element TRIP 57 ms since fault (-1 = no occurance)
Reserved 58–61 For future expansion
1. This register location represents the sequential registers and their numbers within the device itself; as illustrated in Figure 5.1 in Chapter 5, the data
register numbers in the Modbus Master and the DTU3005 unit itself will vary from these register numbers.
2. Status information for each parameter is transmitted in two bits. The status bit indicates status (true = 1, false = 0) for the parameter and the valid bit indi-
cates that the device has sucessfully updated the value in the status bit (true = 1, false = 0).
Device Command Data Retrieved From PLC (7SJ511)
First Command Word (Command Word) Additional Command Words (Data or Value)
0 = No command Unused
1 = Time Sync 2nd Word: Time [ms] - (0-59999)
3rd Word: Time [h/m] - high byte: HH (1-24), low byte: MM (0-59)
4th Word: Date [m/d] - high byte: MM (1-12), low byte: DD (1-31)
5th Word: Date [y] - YY (00-99)
2 = Reset LEDs Unused
3 = Activate Parameter Set A Unused
4 = Activate Parameter Set B Unused
5 = Activate Parameter Set C Unused
6 = Activate Parameter Set D Unused
10 = General Command 2nd Word: [Typ] in high byte, [Inf] in low byte
Real-Time Device Data Stored in PLC (7SJ511) (Continued)
Function Register Location in
PLC Block
1
Range or Contents