5 Creating Project Files—Modbus Master to Devices
Siemens Energy & Automation, Inc. 29
5.2 Configuring the Project File
Once you have created or opened the project file,
select Edit from the main menu. When the Device Pro-
tocol for port 2 is set to SEAbus (see Section 5.4), the
following menu items appear:
Port 1 (Modbus Master)—allows you to select the
protocol (RTU or ASCII) and configure the com-
munications settings for the Modbus Master
device connected to port 1.
Port 2 (Devices)—allows you to configure commu-
nications settings for SEAbus devices or Siemens
Protective relays connected to port 2.
Port 3 (Modbus/Passthrough)—allows you to
select whether port 3 is used as a passthrough to
the devices on port 2, or used for connection to a
second Modbus Master device.
Diagnostics—allows you to indicate if you want
the DTU3005 to write communications diagnostic
information to the Modbus Master.
Device Command Registers—allows you to indi-
cate which PLC registers will be used for device
commands.
Device Defaults—allows you to set the default
data registers for more than one device of a cer-
tain type, e.g., set the defaults for all 4720 power
meters or all S7-I/O units. The data registers can
still be customized for each device, as required.
See Section 5.7.2 for more information.
Device List—allows you to indicate which SEAbus
devices or Siemens protective relays are con-
nected to port 2 and which PLC registers they are
communicating with.
Note: If the Device Protocol for port 2 is set to
VDEW (see Section 5.4), then two addi-
tional menu items are available: Global
Command Registers and Device Text to
Values Table. See Section 5.8 and Section
for instructions on using these menu items.
In addition, the port 3 menu item is
changed to Port 3 (Modbus Master)
because the passthrough feature is not sup-
ported with VDEW devices. The instructions
in Section 5.3 are applicable to port 1 and to
port 3 for VDEW devices.