Appendix A: Supported PLCs
60 Siemens Energy & Automation, Inc.
configured to do so by performing the following steps
when configuring the PLC Port in the DTU3005 Editor
Program:
1. Select “RTS Delay” in the RTS Control selection box.
2. Set the RTS Delay time to 2 ms.
A.9 Modbus PLCs and Devices
Registers Accessed
The DTU3005 will only access registers in the Holding
Area of PLC memory (40001 to 49999). When entering
register numbers, only the offset into this area (1-9999)
should be entered. For example, to access register
number 40001, the value 1 should be entered. To
access register number 49999, the value 9999 should
be entered.
A.10 Omron PLCs
Registers Accessed
The DTU3005 will only access registers in the Data
Area of PLC memory (DM0 to DM9999). When entering
register numbers, only the offset into this area (0-
9999) should be entered. For example, to access regis-
ter number DM1, the value 1 should be entered. To
access register number DM9999, the value 9999
should be entered.
PLCs/Protocols Supported
The DTU3005 will communicate with any Omron PLC
that uses the Host Link Protocol. On many PLCs, this
requires the use of a Host Link Module.
A.11 Siemens S7-200 PLCs
Registers Accessed
The DTU3005 will only access registers in the V-Mem-
ory area of PLC memory (VB0 to VB9999) which are 8-
bit registers. Because the DTU3005 will only read and
write 16-bit values, it will use two consecutive 8-bit
registers in Siemens S7 PLCs to form a 16-bit value.
The first of these consecutive registers must be
located on an even boundary (i.e. VB0, VB2, etc.). The
low order byte of the 16-bit value is located in the low-
est numbered register and the high order byte is
located in the highest numbered register. These regis-
ters can also be accessed in the PLC program or in
Charts as 16-bit registers VW0, VW2, VW4, etc.
When entering register numbers, only the offset into
the V-Memory area (0-9998) should be entered. For
example, to access register number VW0 (VB0 and
VB1), the value 0 should be entered. To access register
number VW9998 (VB9998 and VB9999), the value 9998
should be entered.
Protocol Information
The DTU-3000 follows the Point-to-Point (PPI) protocol
specification for token passing masters used with Sie-
mens S7-200 PLCs. It will operate on a PPI network
along with other masters.
The fully implemented, multi-master version of the PPI
protocol is very slow because of the token passing.
Therefore, a unique feature has been implemented on
the DTU3005 which allows it to run as a single master
with no token passing. This feature can only be used
when no other masters are present on the PPI net-
work. To activate this feature, enter the value 125 into
the DTU Address field on the PLC Port configuration
screen in the DTU3005 Editor Program. Whenever the
DTU Address (address which it resides at on the PPI
network) is set to 125, it will act as a single master.
Passthrough Port
For Siemens S7-200 PLCs, there is an additional
advantage to the “Passthrough” port of the DTU3005.
It allows a non-token passing master such as a per-
sonal computer running Micro/DOS to have access to
a multiple-master token passing network without the
requirement for an MPI card in the personal computer.
This feature can only be used when the DTU Address
is not set to 125 (see above).
A.12 Square D Model 100-700 PLCs
Registers Accessed
The DTU3005 will only access registers in the Data
Area of PLC memory (S10 to S9999). When entering
register numbers, only the offset into this area (10-
9999) should be entered. For example, to access regis-
ter number S10, the value 10 should be entered.
A.13 Square D TSX07 PLCs
Registers Accessed
The DTU3005 will only access registers in the Memory
Word Area of PLC memory (%MW0 to %MW999).
When entering register numbers, only the offset into
this area (0-999) should be entered. For example, to
access register number %MW0, the value 0 should be
entered. To access register number %MW999, the
value 999 should be entered.
A.14 TI505 Series PLCs
Registers Accessed
The DTU3005 will only access registers in the V Area
of PLC memory (V1 to V9999). When entering register
numbers, only the offset into this area (1-9999) should
be entered. For example, to access register number
V1, the value 1 should be entered. To access register
number V9999, the value 9999 should be entered.
Passthrough Port
When using TISOFT PLC programming software on
the passthrough port (Port 3) of the DTU3005, the soft-
ware must be invoked with the following parameters: