Commissioning and optimization (software)
7.5 Commissioning of the fail-safe functions
ET 200pro FC
Operating Instructions, 11/2007, A5E01100763B AA
115
7.5 Commissioning of the fail-safe functions
General steps
Those parameters that are marked with an asterisk ("*") offer a wider variety of setting
options than the ones listed here. For information on additional setting options, please refer
to the List Manual.
When making changes to fail-safe functions, the following steps are mandatory:
Parameter Description Unit Standard
value
Min. Max.
P0010 = 95 Commissioning parameter*
95: Commissioning of fail-safe functions
0 0 95
P9761 SI password input
These parameters are used to enter the security password
necessary for accessing and changing fail-safe function
parameters.
- 0 1000 99999
Change the required fail-safe parameters and then follow the steps below to exit parameterization:
P9799 Checksum for SI parameters
Checksum of fail-safe function parameters.
Enter the value from r9798.
- 0000h 0000h FFFFh
P9899 Checksum for SI parameters
Checksum of fail-safe function parameters.
Enter the value from r9898.
- 0000h 0000h FFFFh
P3900 = 10 End of safety commissioning*
10: Accept changes to fail-safe function parameters.
11: Reject changes to fail-safe function parameters.
0 0 11
Parameters for fail-safe functions
The table below provides an overview of all the fail-safe function parameters. Access level 3
applies in respect of the fail-safe parameters (P0003 = 3). The values of fail-safe parameters
can only be changed with a password (P9761). For a more detailed description, please refer
to the List Manual.
CUs with integrated fail-safe functions are equipped with two processors. To distinguish
between them, they shall be referred to as follows:
● P1 denotes processor 1.
● P2 denotes processor 2.