Configuration / project engineering
5.3 Configuring the communication
ET 200pro FC
72 Operating Instructions, 11/2007, A5E01100763B AA
Figure 5-21 Setting the device-specific parameters
5.3.3 Creating a fail-safe configuration in SIMATIC Manager
Description
A configuration is carried out using the fail-safe I/O module F-Switch or F-RSM on
PROFIBUS DP. The procedure with PROFINET IO is similar and will not be described
separately.
Technical functions and the connections of the F-Switch and F-RSM are described
respectively in the manual
ET 200pro Distributed I/O Devices - Fail-safe Modules
and in the
manual
SIMATIC-ET 200pro Motor Starters
.
Requirements
The following preconditions exist for the configuring and parameterizing of ET 200pro fail-
safe modules:
STEP 7 V 5.3 SP3 or higher
S7 Distributed Safety V5.4 or higher (F Configuration Pack V5.5 SP1 or higher)
S7 F systems V5.2 SP2 or higher
The F Configuration Pack can be downloaded from the Internet
(www.siemens.com/automation/service&support).
Procedure
Once the IM154-2 HF has been positioned and parameterized in the master system, a
module that can control the safety functions of the frequency converter using switch-off
signals in the backplane bus is positioned to the left of the frequency converter.
A fail-safe module (F-Switch or F-RSM) is then plugged in.
Follow the usual procedure with STEP 7 HW Config to configure fail-safe modules (in the
same way as standard ET 200pro modules).