Series commissioning and operation
8.1 Transfer of the frequency converter parameter assignment
ET 200pro FC
132 Operating Instructions, 11/2007, A5E01100763B AA
WARNING
In acknowledging fault F00395, the user assumes full responsibility for the parameters
saved in the frequency converter. In the "Ready to run" state, the frequency converter
can be started after acknowledgement by means of an OFF1/ON command.
F00395 for fail-safe frequency converter
In the case of frequency converters with integrated fail-safe functions, it is necessary to
perform an acceptance test. To clear F00395 on a frequency converter with integrated fail-
safe functions, proceed as follows:
● P0010 = 30
● P9761 = Fail-safe password
● Setting P7844 = 0 (confirmation of parameter download) or
● Setting P7844 = 2 (rejection of parameter download)
→ The frequency converter must be commissioned.
● Fault F00395 is acknowledged automatically by both P7844 settings.
● Perform an acceptance test.
WARNING
In acknowledging fault F00395, the user assumes full responsibility for performing the
acceptance test. The frequency converter must not be switched on before an
acceptance test is properly completed. In the "Ready to run" state, the frequency
converter can be started by means of an OFF1/ON command.