Description
2.2 Components for assembling a frequency converter
ET 200pro FC
26 Operating Instructions, 11/2007, A5E01100763B AA
Table 2-2 Components of the fail-safe frequency converter with F-RSM
Illustration Components Function
1 Rack, wide The ET 200pro bus modules, onto which the electronic modules are
screwed, must be mounted on the rack.
Lengths: 0.5 m, 1 m
2 Interface module for
PROFINET DP, with bus
module
The interface module interconnects the ET 200pro with the DP master and
prepares the data for the electronic modules.
The unit is delivered with the terminating module, and the interface module
is already mounted on the bus module.
• The bus module is the mechanical and electrical connection element
between the various ET 200pro modules.
• The terminating module terminates the ET 200pro.
The following interface modules are available for PROFIBUS DP:
• IM154-1 DP
• IM154-2 DP HF
3 Connection modules for
interface modules
The connection modules are mounted on the interface modules. They are
used to connect PROFIBUS DP, the electronics/encoder supply and the
load voltage supply.
Available connection modules:
• Direct connection:
– CM IM DP Direct
• ECOFAST:
– CM IM DP ECOFAST Cu
– CM IM DP M12, 7/8"
Not
illustrated
Interface module for
PROFINET IO, with bus
module
The interface module interconnects the ET 200pro with the IO controller and
prepares the data for the electronic modules.
The interface module and connection module are shipped as a compact
unit. The terminating module is included. The interface module is mounted
on the bus module.
Interface module available for PROFINET IO:
• IM154-4 PN HF
4 Safety Local repair switch
module (F-RSM), with bus
module
The F-RSM is used to trigger the safety functions of the fail-safe frequency
converter through the backplane bus; it switches the power bus for the
following motor starters and frequency converters. An F-RSM must always
be plugged in the system to the left of the frequency converter and can be
controlled only through local safe inputs (Safety Local function).
5 Frequency converter with bus
module
The frequency converter is connected to the higher-level controller by way
of the bus module and interface module; power and motor are connected
using prefabricated cables
6 Terminating module The ET 200pro bus is terminated with the terminating module