Configuration / project engineering
5.3 Configuring the communication
ET 200pro FC
Operating Instructions, 11/2007, A5E01100763B AA
65
Figure 5-10 Setting the device-specific parameters
5.3.2 Generating a hardware configuration for PROFINET in the SIMATIC Manager
Description
The following example of an ET 200pro FC frequency converter with an "IM 154-4 PN HF"
interface module will be used to demonstrate how to generate a PROFINET configuration
with HW Config in the SIMATIC Manager. This will take place in three steps:
● Parameterizing the PROFINET IO interface in SIMATIC S7
● Equipping the ET 200pro station
● Settings for the frequency converter
Note
Please refer to the "Interface modules" chapter in the manual entitled "ET 200pro
Distributed I/O System" for information on the interface modules.
Parameterizing the PROFINET IO interface in SIMATIC S7
The hardware configuration is used to parameterize the PROFINET IO interface. When a
CPU with an integrated DP interface or a DP communications processor is selected from the
hardware catalog, a PROFINET IO system is made available in the hardware configuration.
Once the parameters for the IO controller have been set, the slave - in this case, the
ET 200pro station - must be selected from the hardware catalog and positioned on the
PROFINET line. This is done by inserting an IM 154. The PROFINET address of the
ET 200pro station must also be specified in IM 154.
Kommentare zu diesen Handbüchern