Commissioning and optimization (software)
7.6 Performing a reset to factory settings
ET 200pro FC
Operating Instructions, 11/2007, A5E01100763B AA
121
7.6.2 Resetting fail-safe parameters to default values
Description
Safe resetting to factory settings causes all fail-safe parameters to revert to their default
values. Exceptions:
r9760 SI internal password
P9761 SI password input
P9762 SI password change
P9763 SI confirmation of password change
Required parameter settings
Parameter Description (parameter name and factory setting (if this does not vary) in bold)
P0003 = 3 User access level*
1: Standard: Facilitates access to the most frequently used parameters.
2: Extended: Facilitates extended access, e.g., to converter I/O functions.
3: Expert level: Only to be used by experts.
P0004 = 0 Parameter filter*
0: All parameters
P0010 = 30 Commissioning parameter*
0: Ready
30: Factory setting, parameter transfer
P9761 SI password input
Enter security password
P0970 = 10 Reset to factory settings*
0: Disabled
1: Reset application parameters
10: Reset parameters for fail-safe functions
BUSY Once the reset to factory settings has been completed, P0970 and P0010 are set to
0.