Additional Information CLV61x Dual Port (PROFINET IO)
8017978 / 2014-11-20 © SICK AG · Germany · All rights reserved · Subject to change without notice 14
4.3 Assigning PN names automatically
The PN name can be automatically assigned by the PROFINET IO Controller (PLC), if:
a) This has been activated in the CPU (is activated by default):
Support device replacement without exchangeable medium = active
b) The topology has been taught-in. A PN partner is then firmly assigned to each used port.
c) The switches used must support this function, e.g., Scalance X200 series.
If a PN device is connected with an empty name and its type matches, the PN name stored on the
PROFINET IO Controller (PLC) is assigned. See also Chapter 3.4 Device replacement.