Cables for PROFIBUS RS485 networks
5.6 FC robust cable (with PUR jacket)
PROFIBUS Network Manual
System Manual, Edition 04/2009, C79000-G8976-C124-03
123
Resistant to water and steam
The jacket material is flammable
Use
The bus cable with the PE jacket is particularly suited for use in the food, beverages and
tobacco industry. It is designed for fixed installation within buildings (inhouse cabling).
5.6 FC robust cable (with PUR jacket)
,QQHUFRQGXFWRU
VROLGFRSSHU
7LQSODWHGFRSSHUEUDLG
VKLHOG
$OXPLQXPIRLO
3ODVWLFIRLO
)LOOHU
385RXWHUMDFNHW
&HOOXODU3(
LQVXODWLRQVOHHYH
Figure 5-5 Structure of the bus cable with PUR jacket
FC bus cable with PUR jacket 6XV1 830-0JH10
The FC bus cable with a PUR jacket 6XV1 830-0JH10 complies with the specification
IEC 61158-2 / EN 61158-2, cable type A, with solid copper cores (AWG 22). The inner
structure of the cable (cores, filler, shielding) is identical to that of the standard cable.
The structure of the cable allows the use of the FastConnect (FC) stripping tool for fast
stripping of the cable, see Section
Installation instructions for SIMATIC NET PROFIBUS
FAST CONNECT (Page
138).
Properties
The characteristics of the PUR jacket material differ from those of the standard bus cable as
follows:
Improved resistance to abrasion
Improved resistance to oil and lubricants
Resistant to UV radiation
The jacket material is flame resistant