Network configuration
3.1 Configuring electrical networks
PROFIBUS Network Manual
System Manual, Edition 04/2009, C79000-G8976-C124-03
47
3.1.5 Configuring electrical networks with RS-485 repeaters
RS-485 repeater
To increase the number of nodes (>32) in a network or to extend the cable length between
two nodes, segments can be connected together using RS485 repeaters to form a network.
The following figure shows a possible combination of several segments using repeaters to
form a network.
The RS-485 repeaters support all transmission speeds from 9.6 kbps to 12 Mbps.
OP 25
S7-300
PG
ET-200S
Repeater
S7-300
S7-300
OP 25
OP 25
ET-200M
OP 25
OP 25
ET-200M
ET-200S
OP 25
Figure 3-1 Structure of an electrical PROFIBUS network using RS485 repeaters