Siemens RS-485 Wartungshandbuch Seite 86

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 350
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 85
Active components
4.2 Active components for optical networks
PROFIBUS Network Manual
86 System Manual, Edition 04/2009, C79000-G8976-C124-03
4.2.2 Optical Link Module OLM
Figure 4-14 Optical Link Module (OLM)
Area of application
With the PROFIBUS OLM (Optical Link Module), Version 4, PROFIBUS networks can be
implemented as bus, star and redundant ring structures.
The transmission rate of a fiberoptic path is not dependent on the distance and can range
from 9.6 kbps to 12 Mbps.
OLMs can be used in system buses based on PROFIBUS, interbuilding networks with glass
fiberoptic cables, mixed networks with electrical and optical segments, largespan networks
(road tunnel, traffic control systems), networks in which high availability is required
(redundant ring networks) etc.
Design
OLMs are available with one or two fiberoptic interfaces for different types of fiberoptic cable:
Plastic fiber-optic cables (980/1000 µm) can be used for single lengths of up to 80 m.
They can be fitted with BFOC connectors on site.
PCF fiber-optic cables (200/230 µm) can be used for single lengths of up to 400 m. They
are offered preassembled with four BFOC plugs and an insertion tool.
Glass fiber multimode fiber-optic cables (62.5/125 µm) such as the SIMATIC NET fiber-
optic cables can be used for long distances of up to 3000 m. They must be ordered
preassembled with 4 BFOC connectors and are tested before they are supplied.
Single mode fiberoptic cables (10/125 μm fibers) can be used for extremely long
distances of up to 15 km. These are available on request.
OLMs can be combined via an RS485 interface and individual nodes or entire electrical
segments can be included in the PROFIBUS network.
Version 4 OLMs support all PROFIBUS transmission speeds up to 12 Mbps.
They have a compact metal casing. They are suitable for installation on a DIN rail or for fixed
mounting. When installed vertically, OLMs can be placed sidebyside needing gaps between
them.
Seitenansicht 85
1 2 ... 81 82 83 84 85 86 87 88 89 90 91 ... 349 350

Kommentare zu diesen Handbüchern

Keine Kommentare