Active components
4.1 Active components for RS485 networks
PROFIBUS Network Manual
76 System Manual, Edition 04/2009, C79000-G8976-C124-03
Installation on a standard rail
To be able to install the repeater on a standard rail, the catch must be present on the back of
the RS485 repeater:
Fit the RS485 repeater onto the standard rail from above and
Push it towards the back until the catch locks it in place.
Removal from the standard rail
To remove the RS-485 repeater from the standard rail:
Press down the catch on the bottom of the RS485 repeater using a screwdriver and
Pull the RS485 repeater out and upwards to remove it from the standard rail.
4.1.1.4 Ungrounded operation of the RS-485 repeater
Ungrounded operation
Ungrounded operation means that chassis and PE are not connected.
Ungrounded operation of the RS485 repeater allows you to operate electrically isolated bus
segments.
The figure shows the change in the voltage relationships resulting from using the RS-485
repeater.
6LJQDOVXQJURXQGHG
6LJQDOVJURXQGHG
Figure 4-9 Ungrounded operation of bus segments
4.1.1.5 Connecting the power supply
Cable type
To connect the 24 V DC power supply, use flexible cables with a cross section of 0.25 mm
2
to 2.5 mm
2
(AWG 26 to 14).
Connecting the power supply
To connect the power supply of the RS-485 repeater:
Strip the insulation from the cable for the 24 V DC power supply.
Connect the cable to terminals "L+", "M" and "PE".