Active components
4.4 Active components for interfacing to PROFIBUS PA
PROFIBUS Network Manual
94 System Manual, Edition 04/2009, C79000-G8976-C124-03
Definition
The DP/PA link consists of the IM 153-2 and up to a maximum of five DP/PA couplers. The
DP/PA link is a DP slave at the PROFIBUS DP end and a PA master at the PROFIBUS PA
end.
Application
With the DP/PA link, you have a decoupled interface from PROFIBUS PA to PROFIBUS DP
with transmission speeds of 9.6 kbps to 12 Mbps.
The following figure shows where the DP/PA Link fits in.
"Programming, operating and
monitoring"
SIMATIC PCS 7 or third-party tool for
parameter assignment
PDM or other tool for
parameter assignment
Cell level
Field level
Management
level
DP-PA coupler Ex
Field devices of PROFIBUSPA
Industrial Ethernet
PROFIBUS-DP
IM 153
PROFIBUS-PA
DP/PA-Link
ET 200X
S7-DP-MasterGateway S7 400
Figure 4-19 Integration of the DP/PA Link
The DP/PA Link is configured with STEP 7, Version 4.02 or higher.
Properties
The DP/PA Link has the following characteristics:
Diagnostics with LEDs and the user program
DP slave and PA master
Can be operated at all transmission speeds (9.6 kbps to 12 Mbps)
Mode of operation
The following figure shows how the DP/PA Link functions with the IM 153-2
(6ES7 153-2BA82-0XB0) and the DP/PA couplers.
The DP/PA Link maps the underlying PROFIBUS PA system on a DP slave.
With the DP/PA Link, PROFIBUS DP is completely decoupled from PROFIBUS PA.