Devices for Special Applications
Load Management
Load Management
8/2
Siemens ET G1 · 10/2008
■
Technical specifications
■
Selection and ordering data
Type Description
N 360 N 360 peak load limiters
1)
• For peak load limitation in plants with tariff-based power
measurement
• Value of an energy pulse configurable in watthours
• Configurable peak load limit of 30... 1000 kW, with configurable
warning limit of 25 ... 1000 kW
• Configurable measuring period of 15, 30 or 60 minutes for the
calculation of the power mean value
• Configurable cycle time of 15, 30, 60, 120 or 240 seconds for
the load extrapolation interval
• Up to 120 loads assignable to peak load limitation
• State monitoring and switching of loads over the KNX
• With parameters assignable per load
• Power consumption of the load
• Turn-off priority (1 ... 10)
• Release/locking of load
• Minimum make time
• Minimum break time
• Maximum break time
• Number of permissible switching cycles in 24 h
• Transmission of extrapolation data via KNX after each
extrapolation
• Transmission of statistics data via KNX at the end of each
measuring period
• 3 LEDs for display of availability (operational voltage), of an
impending exceeding of the maximum value and of a
missing synchronization pulse
• 5 LEDs for display of the current time interval within the
measuring interval
• 8 LEDs for status indication of the first 8 loads
• Inputs for connection of energy pulses generated by utility
company counters and for connection of synchronous
pulses and high/low-tariff contacts
• Electronics powered over an integrated power supply unit for
230 V AC
• Integrated bus coupling units
• Bus connection over bus terminal and contact system to
data rail
• Modular installation devices for mounting on
TH35 EN 60715 mounting rail
• Width 4 MW (1 MW = 18 mm)
1)
Like the documentation, the statistics software for the peak load limiter can be downloaded free of charge from the Internet at:
http://www.siemens.com/gamma-td.
Type Version DT Order No. Price
per PU
PU PS*/
P. uni t
PG Weight
per PU
approx.
Unit(s)Unit(s) kg
5WG1 360-1AB01
N 360 N 360 peak load limiters u
B
5WG1 360-1AB01
11 0300.267
* You can order this quantity or a multiple thereof.
ET_G1_2009_en.book Seite 2 Freitag, 28. November 2008 9:50 09