System Products
Line couplers
14/11
Siemens ET G1 · 10/2008
14
Overview
Classic topology
Modern topology
Innovative topology
LK LK
LK LK
LK LK
LK LK
LK LK
BK BK
Area 1
(West wing)
Line 1.5 Line 2.5
Level 5
Line 1.4 Line 2.4
Level 4
Line 1.3 Line 2.3
Level 3
Line 1.2 Line 2.2
Level 2
Line 1.1 Line 2.1
Level 1
Backbone
line 0.
Area 2
(East wing)
Main line 1.0
Main line 2.0
N 140 line/backbone couplers
for backbone and line connection
I2_14029
1.5.0 2.5.0
1.4.0 2.4.0
1.3.0 2.3.0
1.2.0 2.2.0
1.1.0 2.1.0
1.0.0 2.0.0
KNX
In the classic topology, all the line and
backbone couplers are traditionally
KNX couplers.
This topology is tried and tested and is
widely deployed. The bus cable
lengths are generally limited to a single
building.
LK LK
LK LK
LK LK
LK LK
LK LK
N 146 IP router as backbone coupler
Area 1
(West wing)
Line 1.5 Line 2.5
Level 5
Line 1.4 Line 2.4
Level 4
Line 1.3 Line 2.3
Level 3
Line 1.2 Line 2.2
Level 2
Line 1.1 Line 2.1
Level 1
Area 2
(East wing)
Main line 1.0
Main line 2.0
Data network
(LAN)
I2_14027
1.5.0 2.5.0
1.4.0 2.4.0
1.3.0 2.3.0
1.2.0 2.2.0
1.1.0 2.1.0
1.0.0 2.0.0
KNX
In this modern topology, the backbone
couplers are replaced by N146 IP routers.
In this case (for example), due to the
use of standard network components,
the linking of 2 building sections is no
longer restricted by the lengths of the
bus cable.
Other media, such as optical fiber cables
or W-LAN, can also be used to couple
separate building and for the exchange
of group address telegrams.
LK
LK
LK
LK
LK
LK
LK
LK
LK
LK
N 146 IP router as line coupler
Area 1
(West wing)
Line 1.5 Line 2.5
Level 5
Line 1.4 Line 2.4
Level 4
Line 1.3 Line 2.3
Level 3
Line 1.2 Line 2.2
Level 2
Line 1.1 Line 2.1
Level 1
Data network
(LAN)
Area 2
(East wing)
I2_14028
1.5.0 2.5.0
1.4.0 2.4.0
1.3.0 2.3.0
1.2.0 2.2.0
1.1.0 2.1.0
KNX
In this innovative topology all line
couplers are replaced by
N 146 IP routers.
Backbone couplers are no longer
required. This configuration enables
the linking of each individual building
level over Ethernet (LAN) and through
the utilization of existing LAN networks.
Furthermore, the correct configuration
of the N 146 IP router makes the
commissioning of both large projects
and smaller individual projects quicker
and easier to manage.
An exchange of group address
telegrams is still possible even if
projects are broken down into
individual projects, see chapter
"Application Examples".
ET_G1_2009_en.book Seite 11 Freitag, 28. November 2008 9:50 09