Combination Devices
Input/output devices
4/3
Siemens ET G1 · 10/2008
■
Technical specifications
Type
N 502 N 670/03 N 605 N 605/11 N 526/02 N 266 UP 511/10 UP 562/31
Application program
981501 900501 906101 906202 905303 241C01 207201 207101
Enclosure data
Design N N N N N N UP UP
Modular installation devices for mounting on
TH35 EN 60715 mounting rail
✔
✔ ✔ ✔ ✔ ✔
-- --
For installation in flush-mounting switch and
socket boxes with
∅
= 60 mm and depth = 60 mm
-- -- -- -- -- --
✔ ✔
Dimensions
•Width/
∅
(1 MW = 18 mm) mm 8 MW 4 MW 6 MW 6 MW 6 MW 4 MW
∅
53
∅
53
•Depth mm
28 28
Display/control elements
LED for status indication per input
✔
-- -- --
✔ ✔
-- --
LED for status indication per output
✔
--
✔ ✔ ✔
-- -- --
LED for operation/status indication
✔
--
✔ ✔
-- -- -- --
Pushbuttons for local operation on the device
✔
--
✔ ✔ ✔
-- -- --
Power supply
Electronics powered over an integrated power supply
unit, supply voltage 230 V AC
✔
--
✔ ✔ ✔
-- -- --
Electronics powered over bus voltage
-- -- -- -- -- --
✔ ✔
Electronics powered over an external power supply unit
-- 24 V AC/DC -- -- -- 12 V DC
max.
50 mA
-- --
Bus-dependent operation possible
✔
1)
--
✔ ✔
-- -- -- --
Bus connection
Integrated bus coupling units
✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
Bus connection via bus terminal
✔
✔ ✔ ✔ ✔ ✔ ✔ ✔
Bus connection over contact system to data rail
✔
✔
-- -- -- -- -- --
Outputs
Control output
1 ... 10 V DC -- -- -- -- 3 -- -- --
Max. ECG per output (Osram Dynamic 58 W)
-- -- -- -- 50 -- -- --
Two 12 V outputs "walk test" and "setting/unsetting" for
the control of passive infrared and motion detectors
-- -- -- -- --
✔
-- --
Load output
Floating relay contact
8
2)
2
-- --
3
--
1 2
Silent semiconductor switch -- --
6 6
-- -- -- --
Load types
Rated contact voltage, AC V 230 230 230 230 230 -- 230 230
Rated contact current A
16 10 -- -- 6 -- 16 6
Max. short-time current A
-- -- 1.5 0.5 -- -- -- --
Switching capacity for permanent loading W
-- -- 12 6 -- -- -- --
Protection
Electronic protection of outputs against overload and
short circuit
-- --
✔ ✔
-- -- -- --
Universal inputs/outputs
Adjustable universal inputs/outputs -- 2 -- -- -- -- -- --
Inputs
Max. cable length, unshielded, untwisted m 100 -- 50 50 100
3)
5 5
For signal input (floating contact)
-- --
2 x 3 2 x 3
--
4 2 2
Determination of switching state over the voltage
generated in the device
-- --
✔ ✔
-- --
✔ ✔
For voltage input
(with common ground)
✔
-- -- -- -- -- -- --
• 12 ... 230 V AC/DC
8 -- -- -- -- -- -- --
PT1000 temperature sensor input
--
2
-- -- -- -- -- --
Brightness sensor input for UP 255/AP 255
-- -- -- --
3
-- -- --
1)
Each output affects the output of the same name, adjustable as timer or impulse relay.
2)
Except channel A.
3)
On request.
For selection and ordering data, see page 4/6.