Technical specifications
Type
N 350E REG 371 REG 372 REG 372/02 REG 373
908701 221D01 7F0401 7F0501 7F0601 7F0401 7F0501 7F0601 7F0803
Enclosure data
Modular installation devices for mounting on
TH 35 EN 60715 mounting rail
Dimensions
• Width (1 MW = 18 mm) MW 4 2 6 6 6
Display/control elements
LCD for time, day of the week, daylight saving times,
switching state of channels
3)
Jog pushbuttons for setting the time,
day and program entries
Programming over PC
(N 350E
configurator)
--
(Obelisk)
(Obelisk)
(Obelisk)
Power supply
Electronics powered over bus voltage --
Additional 230 V power supply for integrated DCF77 power
supply unit
-- -- --
Electronics powered over an external
power supply unit for AC/DC
V
12 ... 30 -- -- -- --
Bus connection
Integrated bus coupling units
Bus connection via bus terminal
Connection for DCF77 receiver
-- --
Software
Timer functions
Channels
80
1)
2 4 4 16
Memory locations
2)
36 324 324 500
Standard day/weekly program
No. of weekly progs. that can be prioritized 8 -- 9 9 9
Vacation switching (duration 1 ... 99 days,
preselection 0 ... 99 days)
2)
Random program -- --
Astro program with sunrise and sunset times
-- -- --
Supported telegrams
Switching (1 bit)
Set value (1 byte)
Floating decimal point (2 byte), for temperature, etc.
-- --
-- --
-- --
Positively driven operation (2 bit)
--
Scenes -- 2 -- -- 4 -- -- 4 8
Adjustable cyclic transmission
--
Internal clock, can be synchronized over
master clock by KNX
-- -- --
-- --
--
Transmission of date and time over KNX bus
--
-- --
-- --
Synchronization with DCF77 signal -- -- -- -- -- --
--
Time synchronization over time server in the data network
-- -- -- -- -- -- -- --
1)
Communication objects.
2)
On request.
3)
No daylight saving times, no switching state of the channels.
For selection and ordering data, see page 13/6.