Page 116 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01
mmmmm
Parameters
P006 Empty
Enter distance in units (P005) from the face of the transducer to the process empty point.
P007 Span
Sets the range levels to be measured.
Span is preset for a value close to the maximum available. Enter a value reflecting
maximum application range.
Primary Index Transducer
Values
Range: 0.000 to 9999
Preset: 5.000m (or equivalent depending on units)
Alters •P007 Span
Altered By •P005 Units
Related
• P800 Near Blanking
• P921 material Measurement
• P927 Distance Measurement
Primary Index Level
Values
Range: 0.000 to 9999
Preset: based on Empty (P006)
Alters
• P605 Zero Head
• P112 Relay ON Setpoint
• P113 Relay OFF Setpoint
Altered By
•P005 Units
•P006 Empty
Related
• Volume (P050 to P055)
• P800 Near Blanking
• P921 Material Measurement
• P922 Space Measurement
• P926 Head Measurement
Setting this value also sets Span (P007)
unless Span was already set to another
value. For distance operation (P001=3),
Span is preset to Empty.