Page 70 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01
mmmm
m
Open Channel Monitoring
Palmer Bowlus Flume
Application Information
Sized by pipe diameter D
Flume relief is trapezoidal
Designed to install directly into pipelines and manholes
Head is referenced to bottom of the throat, not bottom of the pipe
For rated flows under free flow conditions, the head is measured at a distance of
D/2 upstream from the beginning of the converging section
Parameter Index Value
P600 G 2–Palmer Bowlus Flume
P602 1 Flume width (D)
P603 G Maximum Head (preset = P007)
P604 G Maximum Flow
P605 G Zero Head
P606 G Time Units
P006
P007
P605
P603
Transducer
D/2, point of
measurement
Flow
Plan View
Front View
Side View