7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 161
mmmmm
Parameters
P605 Zero Head
The distance above Empty (P006) in Units (P005) representing zero head (and zero flow).
Use for most weirs and some flumes (e.g. Palmer Bowlus) where the zero reference is at
a higher elevation than the channel bottom.
P606 Time Units
Determines the units used to display current flow and logging flow values.
This is used when the Primary Measuring Device is Ratiometric (P608=0).
Example:
Primary Index Global
Values
Range: -999 to 9999
Preset: 0.000
Altered By
P005 Units
P007 Span
Related
P006 Empty
P801 Range Extension
P926 Head Measurement
Primary Index Global
Values
1seconds
2minutes
3hours
4* days
Altered By P608 Flowrate Units
Conditions Enter
Flowrate display: millions of gallons/day,
Maximum flowrate is 376,500,000 gallons/day
376.5 for Maximum Flow (P604)
•and 4 for Time Units (P606).
Zero Head (P605)
Empty (P006)
Transducer
Material level at zero flow
PMD base