7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 167
mmmmm
Parameters
P633 LCD Totalized Decimal Position
Enter the maximum number of decimal places to be displayed.
In RUN mode, the number of decimal places displayed is not automatically adjusted.
When LCD Total value exceeds display capabilities, it rolls over to 0 and continues
incrementing.
P640 Remote Totalized Multiplier
Use this feature if the remote totalizer (device connected to the relay set for totalizer
operation [relay Function, P111 = 40]), updates too slowly or rapidly.
Parameter is relevant only if Operation is set to OCM or Pumped Volume (P001 = 6 or 7).
HydroRanger 200 relays have a maximum frequency of 2.5 Hz. Enter the factor (powers of
10 only) by which actual volume is divided, prior to Remote Totalizer count increment.
Example:
For a Remote Totalizer update by 1000s of volume units, enter 3.
Primary Index Global
Values
0 no digits after the decimal point
1 1 digit after the decimal point
2 * 2 digits after the decimal point
3 3 digits after the decimal point
Related LCD Totalizer (P322 and P323)
Note: Set the decimal position during initial commissioning of the
MultiRanger 200. If the position is changed later, the totalizer data in P322 and
P323 will be incorrect and must be reset according to the new decimal value.
Primary Index Global
Values
-3 .001
-2 .01
-1 .1
0*1
Values
110
2100
31000
410,000
5 100,000
6 1,000,000
7 10,000,000
Related
•P001 Operation
P111 Relay Control Function
P115 Relay Interval Setpoint
P645 Relay Duration