Siemens HydroRanger 200 Bedienerhandbuch Seite 149

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 256
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 148
7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 135
mmmmm
Parameters
P133 Pump Power Resumption Delay
Sets the minimum delay before the first pump restarts after power failure.
This reduces the surge from the first pump starting immediately on power resumption.
When this delay expires, other pumps will start as per P132.
P136 Wall Cling Reduction
Varies the upper and lower setpoints to reduce material buildup on the walls.
This value is the range in which the setpoints are allowed to deviate in percent or units.
The Relay Setpoints ON and OFF values are randomly varied inside the range to ensure
that the material level does not consistently stop at the same point
.
Primary Index Global
Values
Range: 0.000 to 9999
Preset: 10 seconds
Related
Advanced Pump Control Modifiers (P130 to P136)
P132 Pump Start Delay
Primary Index Global
Values
Range: 0.000 to 9999
Preset: 0.000
Random Setpoint Range
Level Setpoint ON
Wall Cling Value
Level Setpoint OFF
Seitenansicht 148
1 2 ... 144 145 146 147 148 149 150 151 152 153 154 ... 255 256

Kommentare zu diesen Handbüchern

Keine Kommentare