7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 197
mmmmm
Parameters
Advanced TVT Adjustment (P830 to P835)
The following parameters are for authorized Siemens Milltronics Service personnel or
technicians familiar with Siemens Milltronics echo processing techniques.
Advanced TVT control applies to long shots only.
P830 TVT Type
Selects the TVT Curve used.
Select the TVT type giving the highest confidence (P805) under all level conditions. Use
this parameter with caution. Do not use TVT Slopes with the bF or bLF Algorithm (P820).
P831 TVT Shaper
Turns the TVT Shaper ON or OFF.
Turn the TVT Shaper ON before and after using P832. Turn the TVT Shaper ON and OFF
while monitoring the effect to pick up the true echo.
Primary Index Global
Values
1 TVT Short Curved
2 TVT Short Flat
3TVT Long Flat
4 TVT Long Smooth Front
5 TVT Long Smooth
6TVT Slopes
Altered By •P002 Material
Related
• P805 Echo Confidence
• P835 TVT Slope Min
Primary Index Global
Values
0*off
1on
Related • P832 TVT Shaper Adjust