7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 39
mmmmm
Relays
Reservoir 1
3
Pump up with the following level settings:
Parameter
Relay #
123456
P111 52 52 1(H) 1(L) 0 0
P112 30% 20% 90% 10% – –
P113 80% 80% 85% 15% – –
Reservoir 2
4
Pump up with the following level and rate settings:
Parameter
Relay #
123456
P111 52 52 1(H) 1(L) 0 0
P112 20% 20% 90% 10% – –
P113 80% 80% 85% 15% – –
P121 1
Because the pumps are started by rate you must change P702 to desired
fill rate.
Screen
5
Differential control of a screen or rake:
Parameter
Relay #
123456
P110 312300
P111 50 1(H) 1(L) 1(H) – –
P112 80% 90% 10% 90% – –
P113 20% 85% 15% 10% – –
Alarms
6
General alarms at four setpoints:
Parameter
Relay #
123456
P111 1(H) 1(L) 1(HH) 1(LL) 0 0
P112 80% 20% 90% 10% – –
P113 75% 25% 85% 15% – –
Value # Parameters Affected