7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 185
mmmmm
Parameters
P775 Stop Bits
The number of bits between the data bits.
P778 Modem Available
Sets the HydroRanger 200 to use an external modem.
P779 Modem Inactivity Timeout
Sets the time that the unit will keep the modem connected with no activity.
To use this parameter, ensure that P778 (Modem Available) = 1. Ensure that the value is
low enough to avoid unnecessary delays when an unexpected disconnect occurs but
long enough to avoid timeout while unit is legitimately connected. This parameter value is
ignored by the Modbus Master Drivers, as they automatically disconnect when done.
Hanging Up
If the line is idle and the P779 Modem Inactivity Timeout expires, then the modem is
directed to hang up the line. Ensure that P779 is set longer than the standard polling time
of the connected master device. 0 disables the inactivity timer.
Primary Index Communications Port
Values
Range: 1 or 2
1 * Preset:
Primary Index Communications Port
Values
0 * No modem connected
1Answer only
Primary Index Communications Port
Values
Range: 0-9999 seconds
0 * No timeout
Related
• P778 Modem Available
• P779 Modem Inactivity Timeout