Page 160 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01
mmmmm
Parameters
P603 Maximum Head
The level value associated with Maximum Flow, in Units (P005).
Represents the highest head level supported by the PMD and works in conjunction with
Maximum Flow (P604) to define the highest point in the exponential curve. Use it when
the PMD requires a maximum head and flow reference point. Includes Exponential,
Palmer Bowlus Flume, H-Flume, and Universal Breakpoints.
P604 Maximum Flow
The maximum flowrate associated with Maximum Head (P603).
Represents the flow at the highest head level supported by the PMD and works in
conjunction with Maximum Head (P603) to define the highest point in the exponential
curve. Use when the PMD requires a maximum head and flow reference point. Includes
Exponential, Palmer Bowlus Flume, H-Flume, and Universal breakpoints.
Also use this parameter with Time Units (P606) to define the flowrate units. The limitation
of four digits is for the LCD only, and the flowrate value is available with greater precision
through communications.
Example:
Primary Index Global
Values
Range: -999 to 9999
Preset: Span (P007) value
Altered By
P005 Units
P600 Primary Measuring Device (PMD)
Related
P604 Maximum Flow
P605 Zero Head
Primary Index Global
Values
Range: -999 to 9999
Preset: 1000
Altered By P600 Primary Measuring Device(PMD)
Related
P603 Maximum Head
P606 Time Units
P925 Flow Measurement
Conditions Enter
Flowrate display: millions of gallons/day
Max. flowrate is 376,500,000 gallons/day
376.5 for Maximum Flow (P604)
4 for Time Units (P606)