7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 155
mmmmm
Parameters
P334 Auto Record ON Setpoint
Enter the critical level which, in conjunction with Auto Record OFF Setpoint, defines the
boundaries for Auto Profile Records to be saved.
P335 Auto Record OFF Setpoint
Enter the critical level which, in conjunction with Auto Record ON Setpoint, defines the
boundaries for Auto Profile Records to be saved.
P336 Auto Record Filling / Emptying
Use this feature to restrict Auto Profile Records from being saved unless the level is
rising, falling or either.
If the level changes at a rate in excess of the corresponding Filling / Emptying Indicator
(P702 / P703) values, the Echo Profile is saved subject to this and other Auto Profile
Record restrictions.
Primary Index Global
Values Range: -999 to 9999
Related
P335 Auto Record OFF Setpoint
P336 Auto Record Filling / Emptying
P337 Auto Record LOE Time
Primary Index Global
Values Range: -999 to 9999
Related
P334 Auto Record ON Setpoint
P336 Auto Record Filling / Emptying
P337 Auto Record LOE Time
Primary Index Global
Values
0 * Auto Profile Record on filling or emptying
1 Auto Profile Record on filling only
2 Auto Profile Record on emptying only
Related
P334 Auto Record ON Setpoint
P335 Auto Record OFF Setpoint
P337 Auto Record LOE Time
P702 Filling Indicator
P703 Emptying Indicator