Appendix C: Device Data Format
Siemens Energy & Automation, Inc. 97
General Status Word 3:
1
18 Bit Contents
15 Non-dir. phase O/C prot. is ACTIVE (Valid)
14 Non-dir. phase O/C prot. is ACTIVE (Status)
13 Thermal overload prot.: Current warning (Valid)
12 Thermal overload prot.: Current warning (Status)
11 Thermal Overload Protection is ACTIVE (Valid)
10 Thermal Overload Protection is ACTIVE (Status)
9 50BF-Breaker failure prot. is ACTIVE (Valid)
8 50BF-Breaker failure prot. is ACTIVE (Status)
7 Active Power Exceeded (Valid)
6 Active Power Exceeded (Status)
5 Reactive Power Exceeded (Valid)
4 Reactive Power Exceeded (Status)
3 Power Factor Alarm (Valid)
2 Power Factor Alarm (Status)
1 IL< alarm (Valid)
0IL< alarm (Status)
General Status Word 4:
1
19 Bit Contents
15 Error DC pos Q0 (Valid)
14 Error DC pos Q0 (Status)
13 Error CB/DC pos (Valid)
12 Error CB/DC pos (Status)
11 79 -A/R in LOCKOUT (Valid)
10 79 -A/R in LOCKOUT (Status)
9 79 -A/R is NOT READY (Valid)
8 79 -A/R is NOT READY (Status)
7 79-A/R is BLOCKED (Valid)
6 79-A/R is BLOCKED (Status)
5 67N/67NT-Dir. ground prot. is ACTIVE (Valid)
4 67N/67NT-Dir. ground prot. is ACTIVE (Status)
3 67/67T-Dir. phase prot. is ACTIVE (Valid)
2 67/67T-Dir. phase prot. is ACTIVE (Status)
1 Non-dir. ground O/C prot. is ACTIVE (Valid)
0 Non-dir. ground O/C prot. is ACTIVE (Status)
General Status Word 5:
1
20 Bit Contents
15 Error DC pos Q16 (Valid)
14 Error DC pos Q16 (Status)
13 Error DC pos Q15 (Valid)
12 Error DC pos Q15 (Status)
11 Error DC pos Q10 (Valid)
10 Error DC pos Q10 (Status)
9 Error DC pos Q8 (Valid)
8 Error DC pos Q8 (Status)
7 Error DC pos Q6 (Valid)
6 Error DC pos Q6 (Status)
5 Error DC pos Q5 (Valid)
4 Error DC pos Q5 (Status)
3 Error DC pos Q01 (Valid)
2 Error DC pos Q01 (Status)
1 Error DC pos Q1 (Valid)
0 Error DC pos Q1 (Status)
Real-Time Device Data Stored in PLC (7SJ531) (Continued)
Function Register Location in
PLC Block
Range or Contents