Appendix C: Device Data Format
86 Siemens Energy & Automation, Inc.
C.15 Device Type: 7SD512
Real-Time Device Data Stored in PLC (7SD512)
Function Register Location in
PLC Block
Range or Contents
Operational Measurement:
IL1a
0 %
Operational Measurement:
IL2a
1 %
Operational Measurement:
IL3a
2 %
Operational Measurement: Iea 3 %
Time Delay of Transmission 4 ms
General Status Word 1:
1
5 Bit Contents
15 Parameter set C is active (Valid)
14 Parameter set C is active (Status)
13 Parameter set B is active (Valid)
12 Parameter set B is active (Status)
11 Parameter set A is active (Valid)
10 Parameter set A is active (Status)
9 Device operative/healthy (Valid)
8 Device operative/healthy (Status)
7 >User defined annunciation 4 (Valid)
6 >User defined annunciation 4 (Status)
5 >User defined annunciation 3 (Valid)
4 >User defined annunciation 3 (Status)
3 >User defined annunciation 2 (Valid)
2 >User defined annunciation 2 (Status)
1 >User defined annunciation 1 (Valid)
0 >User defined annunciation 1 (Status)
General Status Word 2:
1
6 Bit Contents
15 AR: Auto-reclose is not ready (Valid)
14 AR: Auto-reclose is not ready (Status)
13 AR: Auto-reclose is blocked (Valid)
12 AR: Auto-reclose is blocked (Status)
11 Emergency O/C protection is active (Valid)
10 Emergency O/C protection is active (Status)
9 Thermal overload prot.: Current warning (Valid)
8 Thermal overload prot.: Current warning (Status)
7 Thermal overload protection is active (Valid)
6 Thermal overload protection is active (Status)
5 Measured value supervision of currents (Valid)
4 Measured value supervision of currents (Status)
3 General internal failure of device (Valid)
2 General internal failure of device (Status)
1 Parameter set D is active (Valid)
0 Parameter set D is active (Status)
General Status Word 3:
1
7 Bit Contents
12–15 Not Used
11 External Trip is Active (Valid)
10 External Trip is Active (Status)
9 Total reception failure (Valid)
8 Total reception failure (Status)
7 CCP blocked by time deviation > 1ms (Valid)
6 CCP blocked by time deviation > 1ms (Status)
5 Transfer Trip function is active (Valid)
4 Transfer Trip function is active (Status)
3 Current comparison protection is active (Valid)
2 Current comparison protection is active (Status)
1 AR: Auto-reclose is dynamically blocked (Valid)
0 AR: Auto-reclose is dynamically blocked (Status)
Number of Last Fault 8 0…32767, 0 = no faults
Fault Date/Time (ms) 9 0…59999 (ms )